Delta VFD110CT43F21A3 Error ovn: Overvoltage at Constant Speed

Delta VFD110CT43F21A3 · taken from the manufacturer’s manual, pages cited

Error codeovn

The ovn code indicates Overvoltage at Constant Speed, where during constant-speed operation the AC motor drive detected an overvoltage on the internal high-voltage DC side. The manual's first action is: “Check that the input voltage is within the drive’s rated input range and monitor for voltage spikes. If the overvoltage is caused by motor inertia regeneration voltage, you can lengthen the deceleration interval or install a braking resistor (optional).”

Model
Delta VFD110CT43F21A3
Display shows
Overvoltage at Constant Speed (ovn)
Type
Error code
Source
Manual p. 297

What ovn means

Overvoltage at Constant Speed p. 297

Common causes

  • During constant‑speed operation, the AC motor drive detected an overvoltage on the internal high‑voltage DC side. 460 V: 900 Vdc. p. 297

What to do

  1. Check that the input voltage is within the drive’s rated input range and monitor for voltage spikes. If the overvoltage is caused by motor inertia regeneration voltage, you can lengthen the deceleration interval or install a braking resistor (optional). p. 297

Before you service the product, read the safety instructions in the manual p. 291.

If ovn is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Delta service.