The GFF code indicates Ground fault, where ground-fault protection circuit is activated when the AC motor drive detects a ground at the output and the ground current exceeds more than 50% of the drive's rated current. The manual's first action is: “Check for short‑circuit or grounding in the motor connection; verify whether the IGBT power module is damaged; inspect output side wiring for poor insulation.”
- Model
- Delta VFD110CT43F21A3
- Display shows
- Ground fault (GFF)
- Type
- Fault code
- Source
- Manual p. 297
What GFF means
Ground fault p. 297
Common causes
- Ground‑fault protection circuit activated. Occurs when the AC motor drive detects a ground at the output and the ground current exceeds more than 50 % of the drive’s rated current. Note: This protection is for the drive, not for personnel. p. 297
What to do
- Check for short‑circuit or grounding in the motor connection; verify whether the IGBT power module is damaged; inspect output side wiring for poor insulation. p. 297
Before you service the product, read the safety instructions in the manual p. 291.
If GFF is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Delta service.
This page summarises what the manufacturer’s manual says about GFF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Delta. Found a mistake? Report an error.