Delta VFD-M Series Error GFF: Ground fault

AC motor drive · taken from the manufacturer’s manual, pages cited

Fault codeGFF

Ground fault means the AC drive output is grounded, which may damage the power module. The manual's first action is: “Remove ground fault”

Model
Delta VFD-M Series
Display shows
Ground fault (GFF)
Type
Fault code
Source
Manual p. 123

What GFF means

Ground fault p. 123

Common causes

  • Is output circuit(cable or motor) of AC motor drive grounded? p. 123
  • Ground fault: The AC drive output is abnormal. When the output terminal is grounded (short circuit current is 50% more than the AC drive rated current), the AC drive power module may be damaged. The short circuit protection is provided for AC drive protection, not user protection. p. 123

What to do

  1. Remove ground fault p. 123
  2. Ground fault: 1. Check whether the IGBT power module is damaged. 2. Check for possible poor insulation at the output line. p. 123

Before you service the product, read the safety instructions in the manual p. 4.

If GFF is still not resolved

  • contact your dealer p. 4
    “If you have any questions, please contact your dealer.”

This page summarises what the manufacturer’s manual says about GFF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Delta. Found a mistake? Report an error.