Fault codeOC
Over current means there is a short circuit or ground fault, or the load is too large. The manual's first action is: “Check if there is any short circuits and grounding between the U, V, W and motor”
- Model
- Delta VFD-M Series
- Display shows
- Over current (OC)
- Type
- Fault code
- Source
- Manual p. 122
What OC means
Over current p. 122
Common causes
- Remove short circuit or ground fault p. 122
- Check if load is too large p. 122
- Suitable torque compensation p. 122
- Check if acceleration time is too short by load inertia p. 122
- Can acceleration time be made longer? p. 122
- Can deceleration time be made longer? p. 122
What to do
- Check if there is any short circuits and grounding between the U, V, W and motor p. 122
- Reduce the load or increase the power of AC motor drive p. 122
- Reduce torque compensation p. 122
- Maybe AC motor drive has malfunction or error due to noise. Please contact with DELTA p. 122
- Increase accel/decel time p. 122
- Check braking method. Please contact DELTA p. 122
- 1. Check whether the motors horsepower corresponds to the AC drive output power. p. 122
- 2. Check the wiring connections between the AC drive and motor for possible short circuits. p. 122
- 3. Increase the Acceleration time (Pr.10, Pr.12). p. 122
- 4. Check for possible excessive loading conditions at the motor. p. 122
- 5. If there are any abnormal conditions when operating the AC drive after short-circuit being removed, it should be sent back to manufacturer. p. 122
Before you service the product, read the safety instructions in the manual p. 4.
If OC is still not resolved
- contact your dealer p. 4 “If you have any questions, please contact your dealer.”
This page summarises what the manufacturer’s manual says about OC; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Delta. Found a mistake? Report an error.