The Delta VFD-M Series reports Over-current during acceleration when there is a short circuit or ground fault, load is too large, or torque compensation is not suitable. The manual's first action is: “Check if there is any short circuits and grounding between the U, V, W and motor”
- Model
- Delta VFD-M Series
- Display shows
- Over-current during acceleration (ocA)
- Type
- Fault code
- Source
- Manual p. 122
What ocA means
Over-current during acceleration p. 122
Common causes
- Remove short circuit or ground fault p. 122
- Check if load is too large p. 122
- Suitable torque compensation p. 122
- Check if acceleration time is too short by load inertia p. 122
- Can acceleration time be made longer? p. 122
- Can deceleration time be made longer? p. 122
- 1. Short-circuit at motor output. 2. Torque boost too high. 3. Acceleration time too short. 4. AC drive output capacity is too small. p. 122
What to do
- Check if there is any short circuits and grounding between the U, V, W and motor p. 122
- Reduce the load or increase the power of AC motor drive p. 122
- Reduce torque compensation p. 122
- Maybe AC motor drive has malfunction or error due to noise. Please contact with DELTA p. 122
- Increase accel/decel time p. 122
- Check braking method. Please contact DELTA p. 122
- 1. Check for possible poor insulation at the output line. 2. Decrease the torque boost setting in Pr.54. 3. Increase the acceleration time. 4. Replace with the AC drive with one that has a higher output capacity (next HP size). p. 122