Delta VFD-M Series Error ocd: Over-current during deceleration

AC motor drive · taken from the manufacturer’s manual, pages cited

Fault codeocd

The Delta VFD-M Series reports Over-current during deceleration when there is a short circuit or ground fault, load is too large, or torque compensation is not suitable. The manual's first action is: “Check if there is any short circuits and grounding between the U, V, W and motor”

Model
Delta VFD-M Series
Display shows
Over-current during deceleration (ocd)
Type
Fault code
Source
Manual p. 122

What ocd means

Over-current during deceleration p. 122

Common causes

  • Remove short circuit or ground fault p. 122
  • Check if load is too large p. 122
  • Suitable torque compensation p. 122
  • Check if deceleration time is too short by load inertia p. 122
  • Can deceleration time be made longer? p. 122
  • 1. Short-circuit at motor output. 2. Deceleration time too short. 3. AC drive output capacity is too small. p. 122

What to do

  1. Check if there is any short circuits and grounding between the U, V, W and motor p. 122
  2. Reduce the load or increase the power of AC motor drive p. 122
  3. Reduce torque compensation p. 122
  4. Maybe AC motor drive has malfunction or error due to noise. Please contact with DELTA p. 122
  5. Check braking method. Please contact DELTA p. 122
  6. 1. Check for possible poor insulation at the output line. 2. Increase the deceleration time. 3. Replace with the AC drive with one that has a higher output capacity (next HP size). p. 122

Before you service the product, read the safety instructions in the manual p. 4.

If ocd is still not resolved

  • contact your dealer p. 4
    “If you have any questions, please contact your dealer.”