The Delta VFD-M Series reports Over-current during deceleration when there is a short circuit or ground fault, load is too large, or torque compensation is not suitable. The manual's first action is: “Check if there is any short circuits and grounding between the U, V, W and motor”
- Model
- Delta VFD-M Series
- Display shows
- Over-current during deceleration (ocd)
- Type
- Fault code
- Source
- Manual p. 122
What ocd means
Over-current during deceleration p. 122
Common causes
- Remove short circuit or ground fault p. 122
- Check if load is too large p. 122
- Suitable torque compensation p. 122
- Check if deceleration time is too short by load inertia p. 122
- Can deceleration time be made longer? p. 122
- 1. Short-circuit at motor output. 2. Deceleration time too short. 3. AC drive output capacity is too small. p. 122
What to do
- Check if there is any short circuits and grounding between the U, V, W and motor p. 122
- Reduce the load or increase the power of AC motor drive p. 122
- Reduce torque compensation p. 122
- Maybe AC motor drive has malfunction or error due to noise. Please contact with DELTA p. 122
- Check braking method. Please contact DELTA p. 122
- 1. Check for possible poor insulation at the output line. 2. Increase the deceleration time. 3. Replace with the AC drive with one that has a higher output capacity (next HP size). p. 122
Before you service the product, read the safety instructions in the manual p. 4.
If ocd is still not resolved
- contact your dealer p. 4 “If you have any questions, please contact your dealer.”
This page summarises what the manufacturer’s manual says about ocd; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Delta. Found a mistake? Report an error.