Delta CP2000 Error gff: Ground fault

Variable frequency drive · taken from the manufacturer’s manual, pages cited

Fault codegff

Ground protection circuit activated. When the AC motor drive detects that the output is grounded and the ground current exceeds more than 50 % of the drive's rated current. The manual's first action is: “Check for short circuits or grounding in the motor connection; verify whether the IGBT power module is damaged; inspect output side wiring for poor insulation.”

Model
Delta CP2000
Display shows
Ground fault (gff)
Type
Fault code
Source
Manual p. 333

What gff means

Ground fault p. 333

Common causes

  • Ground protection circuit activated. When the AC motor drive detects that the output is grounded and the ground current exceeds more than 50 % of the drive's rated current. Note: this protection is for the AC motor drive, not for personnel. p. 333

What to do

  1. Check for short circuits or grounding in the motor connection; verify whether the IGBT power module is damaged; inspect output side wiring for poor insulation. p. 333

Before you service the product, read the safety instructions in the manual p. 327.

If gff is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Delta service.

This page summarises what the manufacturer’s manual says about gff; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Delta. Found a mistake? Report an error.