Delta CP2000 Error ovn: Ov at normal SPD

Variable frequency drive · taken from the manufacturer’s manual, pages cited

Error codeovn

During constant‑speed operation, the AC motor drive detects an overvoltage on the internal DC high‑voltage side. 230 V: 450 Vdc; 460 V: 900 Vdc. The manual's first action is: “Check whether the input voltage is within the drive's rated input range and monitor for voltage spikes. If the overvoltage is caused by motor inertia regeneration voltage, you can lengthen the deceleration interval or install a braking resistor (optional).”

Model
Delta CP2000
Display shows
Ov at normal SPD (ovn)
Type
Error code
Source
Manual p. 334

What ovn means

Ov at normal SPD p. 334

Common causes

  • During constant‑speed operation, the AC motor drive detects an overvoltage on the internal DC high‑voltage side. 230 V: 450 Vdc; 460 V: 900 Vdc. p. 334

What to do

  1. Check whether the input voltage is within the drive's rated input range and monitor for voltage spikes. If the overvoltage is caused by motor inertia regeneration voltage, you can lengthen the deceleration interval or install a braking resistor (optional). p. 334

Before you service the product, read the safety instructions in the manual p. 327.

If ovn is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Delta service.