Overcurrent during deceleration; during deceleration, output current exceeds three times the inverter's rated current. The manual's first action is: “Check whether the U‑V‑W wiring to the motor has poor insulation; increase deceleration time; replace with a higher‑output‑capacity AC motor drive.”
- Model
- Delta CP2000
- Display shows
- Oc at decel (ocd)
- Type
- Error code
- Source
- Manual p. 333
What ocd means
Oc at decel p. 333
Common causes
- Overcurrent during deceleration; during deceleration, output current exceeds three times the inverter's rated current. p. 333
What to do
- Check whether the U‑V‑W wiring to the motor has poor insulation; increase deceleration time; replace with a higher‑output‑capacity AC motor drive. p. 333
Before you service the product, read the safety instructions in the manual p. 327.
If ocd is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Delta service.