During acceleration, the AC motor drive detects an overvoltage on the internal DC high‑voltage side. 230 V: 450 Vdc; 460 V: 900 Vdc. The manual's first action is: “Check whether the input voltage is within the drive's rated input range and monitor for voltage spikes. If the overvoltage is caused by motor inertia regeneration voltage, you can lengthen the deceleration interval or install a braking resistor (optional).”
- Model
- Delta CP2000
- Display shows
- Ov at accel (ovA)
- Type
- Error code
- Source
- Manual p. 333
What ovA means
Ov at accel p. 333
Common causes
- During acceleration, the AC motor drive detects an overvoltage on the internal DC high‑voltage side. 230 V: 450 Vdc; 460 V: 900 Vdc. p. 333
What to do
- Check whether the input voltage is within the drive's rated input range and monitor for voltage spikes. If the overvoltage is caused by motor inertia regeneration voltage, you can lengthen the deceleration interval or install a braking resistor (optional). p. 333
Before you service the product, read the safety instructions in the manual p. 327.
If ovA is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Delta service.
This page summarises what the manufacturer’s manual says about ovA; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Delta. Found a mistake? Report an error.
