Delta CP2000 Error oH1: Over heat 1 warn

Variable frequency drive · taken from the manufacturer’s manual, pages cited

Warning codeoH1

The AC motor drive detects that the IGBT temperature is too high, exceeding the protection setpoint: 1–15 HP: 90 °C; 20–100 HP: 100 °C. The manual's first action is: “IGBT overheat warning”

Model
Delta CP2000
Display shows
Over heat 1 warn (oH1)
Type
Warning code
Source
Manual p. 326

What oH1 means

Over heat 1 warn p. 326

Common causes

  • The AC motor drive detects that the IGBT temperature is too high, exceeding the protection setpoint: 1–15 HP: 90 °C; 20–100 HP: 100 °C. p. 326

What to do

  1. IGBT overheat warning p. 326
  2. Check if ambient temperature is too high; check whether the heat sink has foreign objects; verify fan operation; ensure the AC motor drive has sufficient ventilation space. p. 326

Before you service the product, read the safety instructions in the manual p. 327.

If oH1 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Delta service.

This page summarises what the manufacturer’s manual says about oH1; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Delta. Found a mistake? Report an error.