Delta CP2000 Error ovd: Ov at decel

Variable frequency drive · taken from the manufacturer’s manual, pages cited

Error codeovd

During deceleration, the AC motor drive detects an overvoltage on the internal DC high‑voltage side. 230 V: 450 Vdc; 460 V: 900 Vdc. The manual's first action is: “Check whether the input voltage is within the drive's rated input range and monitor for voltage spikes. If the overvoltage is caused by motor inertia regeneration voltage, you can lengthen the deceleration interval or install a braking resistor (optional).”

Model
Delta CP2000
Display shows
Ov at decel (ovd)
Type
Error code
Source
Manual p. 333

What ovd means

Ov at decel p. 333

Common causes

  • During deceleration, the AC motor drive detects an overvoltage on the internal DC high‑voltage side. 230 V: 450 Vdc; 460 V: 900 Vdc. p. 333

What to do

  1. Check whether the input voltage is within the drive's rated input range and monitor for voltage spikes. If the overvoltage is caused by motor inertia regeneration voltage, you can lengthen the deceleration interval or install a braking resistor (optional). p. 333

Before you service the product, read the safety instructions in the manual p. 327.

If ovd is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Delta service.