During deceleration, the AC motor drive detects an overvoltage on the internal DC high‑voltage side. 230 V: 450 Vdc; 460 V: 900 Vdc. The manual's first action is: “Check whether the input voltage is within the drive's rated input range and monitor for voltage spikes. If the overvoltage is caused by motor inertia regeneration voltage, you can lengthen the deceleration interval or install a braking resistor (optional).”
- Model
- Delta CP2000
- Display shows
- Ov at decel (ovd)
- Type
- Error code
- Source
- Manual p. 333
What ovd means
Ov at decel p. 333
Common causes
- During deceleration, the AC motor drive detects an overvoltage on the internal DC high‑voltage side. 230 V: 450 Vdc; 460 V: 900 Vdc. p. 333
What to do
- Check whether the input voltage is within the drive's rated input range and monitor for voltage spikes. If the overvoltage is caused by motor inertia regeneration voltage, you can lengthen the deceleration interval or install a braking resistor (optional). p. 333
Before you service the product, read the safety instructions in the manual p. 327.
If ovd is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Delta service.