Fault code77
ID 1077 - > 5 Connections occurs when more than five active fieldbus or PC tool connections are present, limiting to five at a time. The manual's first action is: “Leave 5 active connections. Remove the other connections.”
- Model
- Danfoss 100 FLOW
- Display shows
- ID 1077 - > 5 Connections (77)
- Type
- Fault code
- Source
- Manual p. 315
What 77 means
ID 1077 - > 5 Connections p. 315
Common causes
- There are more than 5 active fieldbus or PC tool connections. You can use only 5 connections at the same time. p. 315
What to do
- Leave 5 active connections. Remove the other connections. p. 315
If 77 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Danfoss service.
This page summarises what the manufacturer’s manual says about 77; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Danfoss. Found a mistake? Report an error.