Danfoss 100 FLOW Error 105: ID 1105 - Feedback Supervision Fault (ExtPID)

Danfoss 100 FLOW · taken from the manufacturer’s manual, pages cited

Fault code105

ID 1105 - Feedback Supervision Fault (ExtPID) means the feedback value is outside supervision limits or delay settings for ExtPID. The manual's first action is: “Check the process.”

Model
Danfoss 100 FLOW
Display shows
ID 1105 - Feedback Supervision Fault (ExtPID) (105)
Type
Fault code
Source
Manual p. 315

What 105 means

ID 1105 - Feedback Supervision Fault (ExtPID) p. 315

Common causes

  • The feedback value is not in the supervision limits (P3.14.4.2 and P3.14.4.3) and the delay (P3.14.4.4), if you set the delay. p. 315

What to do

  1. Check the process. p. 315
  2. Check the parameter settings, the supervision limits, and the delay. p. 315

If 105 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Danfoss service.

This page summarises what the manufacturer’s manual says about 105; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Danfoss. Found a mistake? Report an error.