SAFE TORQUE OFF (0xFF7A) means the safe torque off function is active, i.e. safety circuit signal(s) connected to connector XSTO is lost. The manual's first action is: “Check safety circuit connections. For more information, see appropriate drive hardware manual, description of parameter 30.07 (page 196), and Application guide - Safe torque off function for ACSM1, ACS850 and ACQ810 drives (3AFE68929814 [English]).”
- Model
- ABB ACQ810
- Display shows
- SAFE TORQUE OFF (0xFF7A) (2003)
- Type
- Alarm code
- Source
- Manual p. 314
What 2003 means
SAFE TORQUE OFF (0xFF7A) p. 314
Common causes
- Safe torque off function is active, i.e. safety circuit signal(s) connected to connector XSTO is lost. p. 314
What to do
- Check safety circuit connections. For more information, see appropriate drive hardware manual, description of parameter 30.07 (page 196), and Application guide - Safe torque off function for ACSM1, ACS850 and ACQ810 drives (3AFE68929814 [English]). p. 314
Before you service the product, read the safety instructions in the manual p. 195.
If 2003 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact ABB service.