ABB ACQ810 Error 0001: OVERCURRENT (0x2310)

Pump control drive · taken from the manufacturer’s manual, pages cited

Fault code0001

OVERCURRENT (0x2310) means output current has exceeded internal fault limit. The manual's first action is: “Check motor load.
Check acceleration times in parameter group **22 Speed ref ramp**.
Check motor and motor cable (including phasing and delta/star connection).
Check that the start-up data in parameter group 99 corresponds to the motor rating plate.
Check that there are no power factor correction capacitors or surge absorbers in motor cable.”

Model
ABB ACQ810
Display shows
OVERCURRENT (0x2310) (0001)
Type
Fault code
Source
Manual p. 321

What 0001 means

OVERCURRENT (0x2310) p. 321

Common causes

  • Output current has exceeded internal fault limit. p. 321

What to do

  1. Check motor load.
    Check acceleration times in parameter group **22 Speed ref ramp**.
    Check motor and motor cable (including phasing and delta/star connection).
    Check that the start-up data in parameter group 99 corresponds to the motor rating plate.
    Check that there are no power factor correction capacitors or surge absorbers in motor cable.
    p. 321

Before you service the product, read the safety instructions in the manual p. 195.

If 0001 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact ABB service.

This page summarises what the manufacturer’s manual says about 0001; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with ABB. Found a mistake? Report an error.