OVERCURRENT (0x2310) means output current has exceeded internal fault limit. The manual's first action is: “Check motor load.
Check acceleration times in parameter group **22 Speed ref ramp**.
Check motor and motor cable (including phasing and delta/star connection).
Check that the start-up data in parameter group 99 corresponds to the motor rating plate.
Check that there are no power factor correction capacitors or surge absorbers in motor cable.”
- Model
- ABB ACQ810
- Display shows
- OVERCURRENT (0x2310) (0001)
- Type
- Fault code
- Source
- Manual p. 321
What 0001 means
OVERCURRENT (0x2310) p. 321
Common causes
- Output current has exceeded internal fault limit. p. 321
What to do
- Check motor load.
Check acceleration times in parameter group **22 Speed ref ramp**.
Check motor and motor cable (including phasing and delta/star connection).
Check that the start-up data in parameter group 99 corresponds to the motor rating plate.
Check that there are no power factor correction capacitors or surge absorbers in motor cable. p. 321
Before you service the product, read the safety instructions in the manual p. 195.
If 0001 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact ABB service.