ABB ACQ810 Error 0006: EARTH FAULT (0x2330)
Programmable fault: **30.05 Earth fault**

Pump control drive · taken from the manufacturer’s manual, pages cited

Fault code0006

EARTH FAULT (0x2330) means drive has detected load unbalance typically due to earth fault in motor or motor cable. The manual's first action is: “Check there are no power factor correction capacitors or surge absorbers in motor cable.
Check that there is no earth fault in motor or motor cables:
- measure insulation resistances of motor and motor cable.
If no earth fault can be detected, contact your local ABB representative.”

Model
ABB ACQ810
Display shows
0006
Type
Fault code
Source
Manual p. 321

What 0006 means

EARTH FAULT (0x2330)
Programmable fault: **30.05 Earth fault** p. 321

Common causes

  • Drive has detected load unbalance typically due to earth fault in motor or motor cable. p. 321

What to do

  1. Check there are no power factor correction capacitors or surge absorbers in motor cable.
    Check that there is no earth fault in motor or motor cables:
    - measure insulation resistances of motor and motor cable.
    If no earth fault can be detected, contact your local ABB representative.
    p. 321

Before you service the product, read the safety instructions in the manual p. 195.

If 0006 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact ABB service.