Start here

Huawei SUN2000 8KTL-28KTL Quick Installation Guide
This guide provides step-by-step instructions for installing Huawei SUN2000 8KTL-28KTL inverters, including mounting on walls or racks, connecting AC and DC cables, and setting up grid parameters. Safety precautions are emphasized, such as using insulated tools and verifying all connections before powering on. The guide also references the full user manual for detailed configurations and includes a grid standard code table for international compatibility.
Installation involves selecting appropriate mounting hardware, securing the inverter, connecting protective grounding, and properly wiring AC and DC inputs. The guide specifies cable cross-sections based on model, and includes warnings against incorrect DC polarity or improper shutdown procedures. After installation, users must verify all connections and set grid parameters such as voltage standards and time settings before connecting to the grid. This manual is written in Chinese.
Huawei SUN2000 8KTL-28KTL specifications
| Weight | 40kg for 8KTL/10KTL/12KTL; 48kg for 15KTL/17KTL/20KTL/23KTL/28KTL |
|---|---|
| Recommended DC Cable Cross-Section | 4.0mm² (12AWG) for 8KTL/10KTL/12KTL; 6.0mm² (10AWG) or 10.0mm² (8AWG) for 15KTL-28KTL |
| AC Output Connector | 4-core outdoor cable (L1, L2, L3, N) for 15KTL-28KTL; 3-core for 28KTL |
All Huawei SUN2000 8KTL-28KTL documents by type
The shortest path to a working setup, usually only a few pages.
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in these manuals
What is the recommended cable cross-section for the DC input?
For 8KTL/10KTL/12KTL models, use 4.0mm² (12AWG); for 15KTL-28KTL models, use 6.0mm² (10AWG) or 10.0mm² (8AWG).
What should I do if I reverse the DC input polarity?
Do not immediately turn off the DC SWITCH. Disconnect the PV string cables or wait until the voltage drops to a safe level, then turn off the DC SWITCH and reconfigure the polarity.
Who is the intended audience for this manual?
This manual is suitable for PV power station operators and electrical technicians with corresponding qualifications.
What safety distance is required during installation?
The inverter requires a minimum clearance of 200mm on the left and right, 500mm above, 300mm below, and 1000mm in front.