Flowline LC52 Series DataPoint Level Sensor Controller User Manual
This manual provides instructions for the Flowline LC52 Series Continuous Relay Controller, a general-purpose device for single tank level indication. It features dual relays (one SPDT and one Latching SPDT) and a 4-20 mA output, allowing for automatic operations like filling or emptying tanks, as well as high or low level alarms. The controller includes a 3.5-digit LED display and can be mounted on a DIN rail or back panel.
Read onlineFlowline LC52 Series specifications
| Supply voltage | 120 V AC (240 V AC), 50 - 60 Hz |
|---|---|
| Consumption | 5 Watt |
| Relay rating | 250 V AC, 10A, 1/2 hp |
| Time delay | 0-60 seconds |
| Temperature range | -40° to 158° F / -40° to 70° C |
| Enclosure mounting | 35 mm DIN (EN 50 022) |
| Enclosure material | Polypropylene (U.L. 94 VO) |
| Relay types | (1) SPDT (1) Latched SPDT |
Source: Flowline LC52 Series Continuous Relay Controller Owner's Manual
All Flowline LC52 Series documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in these manuals
What is the warranty period?
The warranty covers the shorter of one year from purchase or two years from manufacture.
From: Flowline LC52 Series Continuous Relay Controller Owner's Manual
What is the relay contact rating?
The relay is rated for a 10 amp resistive load.
From: Flowline LC52 Series Continuous Relay Controller Owner's Manual
What is the contact rating of the LC52 relays?
The relay is rated for a 12 amp resistive load.
From: Flowline LC52 Series DataPoint Level Sensor Controller User Manual
Can the LC52 controller be mounted on a DIN rail?
Yes, the polypropylene enclosure can be DIN rail mounted or back panel mounted.
From: Flowline LC52 Series DataPoint Level Sensor Controller User Manual