Key facts
- Brand
- AUMA
- Model
- SA 16.2
- Category
- Industrial Robot
- Documents
- 6
- Languages
- DE · EN · ES · SV · NO
- Last added
- 2012-07-10
Start here

AUMA SA 07.2/SA 16.2/SAR 07.2/SAR 16.2 Actuators & AUMATIC AC 01.2 Intrusive Control Unit Manual
This manual provides the required safety instructions, handling, transport, storage and mounting guidelines for the AUMA multiturn actuators (SA 07.2, SA 16.2, SAR 07.2, SAR 16.2) and the AUMATIC AC 01.2 intrusive control unit. It stresses that only trained personnel may perform installation, electrical connection, start‑up and maintenance.
The document contains detailed sections on electrical wiring, manual and motor‑driven operation, positioning, signal lamps, commissioning steps, fault handling, technical data, spare‑parts list and certification information. It also covers special requirements for use in explosive atmospheres (ATEX zone 22) and temperature limits.
AUMA SA 16.2 specifications
| Torque setting range | 400 - 1000 Nm |
|---|---|
| Motor power | 5.0 kW |
| Rated voltage | 400 V 50 Hz 3-ph AC |
| Protection rating | IP68 |
| Operating temperature range | -25°C - +70°C |
Source: AUMA SA 16.2 AC 01.2 Rotary Actuator Technology Data Sheet
All AUMA SA 16.2 documents by type
Ratings, dimensions and ordering codes, for selection and design work.
Disassembly, diagnostics and part numbers, for repair.
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in these manuals
What is the rated power of the motor?
The motor has a rated power of 5.0 kW.
From: AUMA SA 16.2 AC 01.2 Rotary Actuator Technology Data Sheet
What is the torque adjustment range?
The torque can be adjusted between 400 Nm and 1000 Nm.
From: AUMA SA 16.2 AC 01.2 Rotary Actuator Technology Data Sheet
What output drive standards are supported?
The actuators support output drives according to EN ISO 5210, DIN 3210, and DIN 3338.
From: AUMA SA 07.2-SA 16.2 SAR 07.2-SAR 16.2 technology data
Are dimensions dependent on the motor used?
Yes, exact dimensions depend on the specific motor used.
From: AUMA SA 07.2-SA 16.2 SAR 07.2-SAR 16.2 technology data
Which safety standards apply to this product?
The product complies with ATEX 94/9/CE, EN 50281‑1‑1, EN ISO 3691, EN 14502 and DIN 15306/15309.
What safety precautions must be followed when working with the actuator?
All personnel must read and follow the safety instructions, use qualified staff, and comply with applicable standards and regulations.
From: AUMA SA 07.2, SA 16.2, SAR 07.2, SAR 16.2 Operation Manual