Vacon OPTBJ STO and ATEX Option Board Safety Manual

Safety manual for the Vacon OPTBJ option board covering STO/SS1 functions, installation, wiring, and ATEX thermistor monitoring.


Vacon OPTBJ STO and ATEX Option Board Safety Manual - cover page
Brand
Vacon
Category
Industrial Supply
Document type
Service Manual
Language
English
Pages
40
File format
PDF
File size
3.1 MB
Published
23 October, 2026
Updated
23 October, 2026
MD5 checksum
EE6855587FEDAADC1177161944C686D4

About this manual

This document serves as a safety manual for the Vacon OPTBJ option board, which is used with Vacon 100 AC drives. It details the Safe Torque Off (STO) and Safe Stop 1 (SS1) safety functions, including technical data, wiring examples, and commissioning procedures. The manual also covers the thermistor function for ATEX compliance, explaining how the board monitors motor temperature to prevent overheating.

What's inside

  • Approvals
  • General
  • Installation of OPTBJ board
  • OPTBJ board layout
  • STO and SS1 safety functions
  • Commissioning
  • Maintenance
  • Thermistor function (ATEX)

Specifications

STO Safety Integrity LevelSIL3
STO Performance LevelPL"e" Category 3
Overtemperature response time20ms
Overtemperature threshold4 kOhm
Thermistor input terminals28(TI1+) and 29(TI1-)

Frequently asked questions

What standards does the STO safety function comply with?

The STO function complies with EN 61800-5-2 SIL3, EN ISO 13849-1 PL"e" Category 3, EN 62061: SILCL3, and IEC 61508: SIL3.

Can the OPTBJ board be repaired by the user?

No, it is not allowed to perform any repair work on the OPTBJ board; faulty boards must be returned to Vacon for analysis.

What happens if the motor temperature exceeds the overtemperature limits?

Fault 29 (Atex thermistor) is activated, and the drive modulation is disabled within 20ms.