System Sensor EPS10-1 and EPS10-2 Alarm Pressure Switches Data Sheet

System Sensor EPS10-1 and EPS10-2 alarm pressure switches data sheet covers features, specifications, ordering, applications, dimensions, and connections.


System Sensor EPS10-1 and EPS10-2 Alarm Pressure Switches Data Sheet - cover page
Brand
System Sensor
Category
switch
Document type
Datasheet
Language
English
Pages
2
File format
PDF
File size
389 KB
Published
23 November, 2026
Updated
23 November, 2026
MD5 checksum
0C8B9CE1B00174FAD6B9E0C998CB9B5E

About this manual

This data sheet describes System Sensor EPS10 Series alarm pressure switches, including EPS10-1 with one SPDT switch and EPS10-2 with two SPDT switches. They are designed for wet, dry, deluge, and pre-action automatic sprinkler systems to indicate a discharge from a sprinkler.

The document lists agency listings, features, architectural/engineering specifications, ordering information, replacement parts, typical sprinkler applications, basic dimensions, electrical connections, and physical/operating specifications.

What's inside

  • Agency Listings
  • Features
  • Architectural/Engineering Specifications
  • Ordering Information
  • Replacement Parts
  • Typical Sprinkler Applications
  • Pressure Switch Basic Dimensions
  • Electrical Connections
  • Physical/Operating Specifications
  • Service Use

Specifications

Maximum operating pressure300 psi
Operating temperature range–40°F to 160°F (–40°C to 71°C)
Adjustment pressure range4 to 20 psi
Factory settingOperates at rising pressure 4 to 8 psi
EPS10-1 switch contactsOne set SPDT (Form C)
EPS10-2 switch contactsTwo sets SPDT (Form C)
AC contact rating10.0 A, ½ HP @ 125/250 VAC
DC contact rating2.5 A @ 6/12/24 VDC
Enclosure ratingUL 4x, NEMA 4 for indoor or outdoor use
Pressure connection½˝ NPT male glass reinforced nylon
DifferentialApproximately 3 psi throughout range
Dimensions5.12˝ H × 3.325˝ W × 4.250˝ L (13.0 cm × 8.4 cm × 10.8 cm)
Warranty3 years

Frequently asked questions

What are System Sensor EPS10 Series switches designed for?

They are designed for wet, dry, deluge, and pre-action automatic sprinkler systems to indicate a discharge from a sprinkler.

What is the difference between the EPS10-1 and EPS10-2?

The EPS10-1 has a single SPDT switch, while the EPS10-2 contains two SPDT switches.

What pressure range can the EPS10 Series be adjusted to?

It has field adjustable pressure sensitivity for an alarm response between 4 and 20 psi.

What is the factory setting for the EPS10 Series?

It is factory set to respond at 4 – 8 psi on rising or falling pressure.

Download PDF (389 KB)