Installation and maintenance instructions for the System Sensor DNR air duct smoke detector, covering installation, sampling tubes, testing, wiring, and…
This document is the installation and maintenance instructions for the System Sensor Model DNR Air Duct Smoke Detector, which uses photoelectric technology to sense smoke in HVAC air ducts. When sufficient smoke is sensed, an alarm signal is initiated at the fire control panel so fans and blowers can be shut off or air handling systems changed over. The DNR includes a sensor cover tamper feature, two local indication LEDs, a remote alarm output for devices such as the RA100Z annunciator, and remote test capability with the RTS151 or RTS151KEY remote test stations.
The manual covers verifying duct air flow, mounting in rectangular or square configurations, drilling mounting holes, selecting and installing sampling tubes (DST tubes ordered separately by duct width), measurement tests, field wiring, cleaning, sensor replacement, and optional accessories. It notes that duct detectors must not be used as a substitute for open area detector protection, and that the detector should be visually inspected semiannually and functionally tested at least once a year per NFPA 72.
| Operating Temperature | –4° to 158° F (–20° to 70° C); 32° F to 120° F (0° C to 49° C) with module installed in the DNR |
|---|---|
| Storage Temperature | –22° to 158° F (–30° to 70° C) |
| Humidity | 0% to 93% Relative Humidity, non-condensing |
| Air Velocity | 100 to 4000 ft./min. (0.5 to 20.3 m/sec.) |
| Rectangular Footprint Dimensions | 14.38 in L × 5 in W × 2.5 in D (37 cm L × 12.7 cm W × 6.36 cm D) |
| Square Footprint Dimensions | 7.75 in L × 9 in W × 2.5 in D (19.7 cm L × 22.9 cm W × 6.35 cm D) |
| Weight | 1.6 pounds; 0.73 kg |
| Accessory Current Loads (RA100Z) | 0 mA standby, 12 mA max. alarm at 24 VDC |
| Accessory Current Loads (RTS151KEY) | 12 mA standby, 12 mA max. alarm at 24 VDC |
Use DST1 for ducts up to 1 ft., DST1.5 for 1 to 2 ft., DST3 for 2 to 4 ft., DST5 for 4 to 8 ft., and DST10 (2-piece) for 8 to 12 ft. The tube must extend at least 5/8 of the duct width.
The DNR is designed for air handling systems with air velocities of 100 to 4000 feet per minute, and duct widths from 6 inches to 12 feet can be accommodated.
According to NFPA, the detector should be visually inspected semiannually and functionally tested at least once a year, possibly more often depending on the air quality of the duct supply air.
No. The National Fire Protection Association has established that duct detectors must not be used as a substitute for open area detector protection or for early warning in a building's regular fire detection system.