About this manual

The RTS151KEY(A) is an automatic fire detector accessory designed to test remotely located duct and beam detectors. It features a multi-colored LED that indicates power (green) or alarm (red) status. The device is intended for use with specific detector models and requires a test coil for certain models. Installation involves mounting to a single gang box or directly to wall/ceiling, with wiring diagrams provided for various detector types. The device can reset certain detector models, and its operation is controlled via a key switch with TEST, RESET, and NORMAL positions. A three-year limited warranty is provided for defects in materials and workmanship under normal use.

What's inside

  • General Information
  • Operation
  • Wiring Instructions
  • Wiring Diagrams
  • Three-Year Limited Warranty

Specifications

Dimensions4.6˝ H × 2.75˝ W × 1.8˝ D
Weight0.24 Lbs.
Power LED (Green)14 – 35 VDC, 12 mA maximum
Alarm LED (Red)2.8 – 32 VDC, 12 mA maximum
Alarm Response Time40 seconds maximum
Temperature Range–10°C to 60°C (14°F to 140°F)
Humidity95% relative humidity, noncondensing
Max ListingUL, FM, CE

Frequently asked questions

What does the green LED indicate?

Green indicates power and that the detector board is in place.

What does the red LED indicate?

Red indicates alarm.

How do I reset the device?

Turn the key counterclockwise to the “RESET” position and hold. The LED should turn off. Then, turn the key back to the “NORMAL” position and remove.

What models require a test coil?

A test coil is required only for use with D2/DNR/DH400/DH500 models. For D2 models order part # DCOIL. For DH400/500 models order part #Coil.