Installation and maintenance instructions for System Sensor FD-851RE, FD-851HTE and FD-851TE heat detectors.
System Sensor FD-851RE, FD-851HTE and FD-851TE heat detectors use a single thermistor sensing element with ambient temperature compensation and fast response. The document covers general description, specifications, base mounting and wiring, detector installation, testing, maintenance and limitations.
Model FD-851RE is 58°C plus rate of rise, FD-851HTE is 78°C fixed temperature and FD-851TE is 58°C fixed temperature. Features include a bicolour LED, latching alarm reset by momentary power interruption and remote LED annunciator capability as an optional accessory.
| Height | 57 mm (mounted in a B401 base) |
|---|---|
| Diameter | 102 mm |
| Weight | 105 g (excluding base) |
| Normal operating temperature range | -30°C to 70°C |
| FD-851HTE alarm threshold | 78°C |
| Supply voltage | 8 - 30 VDC |
| Air velocity | 20 m/s (4000 ft/min) |
| Humidity | 5 - 95% RH (non-condensing) |
| Quiescent current | 60 µA typical (FD-851HTE 65 µA) |
| Maximum alarm current | 80 mA |
| Latching alarm | Reset by momentary power interruption |
| Certification (FD-851RE) | EN54-5 Class A1R |
| Certification (FD-851TE) | EN54-5 Class A1S |
| Certification (FD-851HTE) | EN54-5 Class BS |
| Installation ambient temperature | 0°C to 50°C for extended periods |
The alarm can only be reset by a momentary power interruption.
A specialised tool such as supplied by No Climb Products Limited.
Use a vacuum cleaner and/or clean, compressed air to remove dust and debris.
It may also be set to flash green.