System Sensor 5600 Series Mechanical Heat Detector Installation and Maintenance Instructions

describe the features and characteristics of the 5600 series mechanical heat detector


System Sensor 5600 Series Mechanical Heat Detector Installation and Maintenance Instructions - cover page
Brand
System Sensor
Category
detectors
Document type
Installation Guide
Language
English
Pages
4
File format
PDF
File size
170 KB
Published
26 October, 2023
Updated
26 October, 2023
MD5 checksum
7FFE5BE84AE63E9140A2166FA21EC4B6

About this manual

System Sensor 5600 Series mechanical heat detectors are intended for property protection or non-life-safety installations where smoke detection is not practical or appropriate. The series includes single- and dual-circuit models with fixed temperature or combination fixed temperature/rate-of-rise sensors, rated at 135°F (57°C) or 194°F (90°C). Fixed temperature models 5603, 5604, 5623, and 5624 are non-resettable; combination models 5601, 5602, 5621, and 5622 have a self-restoring rate-of-rise element that may be tested with a hair dryer or heat gun.

The manual describes mounting bracket options for flush or surface installation, wiring guidelines and diagrams for single- and dual-circuit models, installation steps, and testing/maintenance. It also lists operating voltage and contact ratings, alarm temperatures, rate-of-rise threshold, humidity range, terminal wire size, back box mounting, dimensions, and weight, and includes a three-year limited warranty.

What's inside

  • General Description
  • Non-Resettable Fixed Temperature Sensor
  • Self-Restoring Rate-of-Rise (ROR) Sensor
  • Mounting Bracket
  • Wiring Installation Guidelines
  • Installation
  • Testing/Maintenance
  • Specifications
  • FCC Statement
  • Three-Year Limited Warranty

Specifications

Operating Voltage / Contact Ratings6–125 V AC / 3A (resistive); 6–28 VDC / 1A; 125 VDC / 0.3A; 250 VDC / 0.1A
Alarm Temperature135°F (57°C) for models 5601, 5603, 5621, 5623; 194°F (90°C) for models 5602, 5604, 5622, 5624
Maximum Installation Temperature100°F (38°C) for 5601, 5603, 5621, and 5623; 150°F (65.6°C) for 5602, 5604, 5622, and 5624
Rate-of-Rise Threshold15°F (8.3°C) per minute (models 5601, 5602, 5621, and 5622 only)
Operating Humidity Range5 to 95% RH non-condensing
Input Terminals14–22 AWG
Dimensions with mounting bracketDiameter: 4.57 inches (11.6 cm); height: 1.69 inches (4.3 cm)
Weight6 oz. (170 g)
UL Maximum Spacing (10-foot ceiling)50 ft x 50 ft for combination fixed temperature/rate-of-rise models; 25 ft x 25 ft for fixed temperature models

Frequently asked questions

Which 5600 Series models are dual circuit?

The dual-circuit models are 5621, 5622, 5623, and 5624.

Can the fixed temperature models be tested?

No. Models 5603, 5604, 5623, and 5624 are non-resettable and cannot be tested.

How is the rate-of-rise element tested?

On models 5601, 5602, 5621, and 5622, the self-restoring rate-of-rise element may be tested with a hair dryer or heat gun, as long as the heat source does not exceed the fixed temperature rating.

What wire size do the detector terminals accept?

The non-polarized screw terminals accept 14–22 AWG wire.

Download PDF (170 KB)