MTL MTL1172 Resistance Temperature Device Input Converter Technical Data

The MTL1172 from MTL is a single-channel RTD input converter for PT100 sensors with 4-20mA and 1-5V outputs and switch-selectable input ranges.


MTL MTL1172 Resistance Temperature Device Input Converter Technical Data - cover page
Brand
MTL
Category
Converter
Document type
Datasheet
Language
English
Pages
1
File format
PDF
File size
85 KB
Published
22 November, 2026
Updated
22 November, 2026
MD5 checksum
033727BFC0C85240041487B0F1D3D4DC

About this manual

The MTL1172 from MTL is a single-channel resistance temperature device input converter for PT100 type RTD sensors. It provides 4-20mA or 1-5V outputs, with switch-selectable input ranges and open-wire detection with switch-selectable upscale/downscale drive.

Power is supplied via the power bus embedded in the DIN rail. The PBUS6.2 kit must be ordered separately, and the MTL1991 or PBUS02 is used to feed power onto the bus.

What's inside

  • Technical data
  • MTL signal conditioners
  • MTL1172 resistance temperature device input converter
  • Terminals Function
  • SPECIFICATION
  • common specification

Specifications

Number of channelsOne, with fully floating outputs
Location of sensorSafe area
Input range15 switch selectable ranges; see instruction manual
Output rangeCurrent output 4-20mA or voltage output 1-5V
Open wire detectionSwitch selectable, upscale/downscale drive
Transfer accuracy0.1% of span typical, 0.2% max
Current consumption (current output)37mA @ 24V
Current consumption (voltage output)13mA @ 24V
Power dissipation0.9W @ 24V
Isolation50V ac or dc between power, field and system circuits
Isolation testtested to 840Vac

Frequently asked questions

What sensor type does the MTL1172 support?

It is a one-channel converter for PT100 type RTD sensors.

What output ranges does the MTL1172 have?

It has a 4-20mA current output or a 1-5V voltage output.

How is the MTL1172 powered?

Power is supplied via the power bus embedded in the DIN rail.

What must be ordered separately?

The PBUS6.2 kit must be ordered separately.

Download PDF (85 KB)