The MTL 9189 instruction manual provides installation, safety, wiring, testing and maintenance guidance for the 8‑segment redundant fieldbus power supply.
This manual explains the installation, commissioning, and routine maintenance procedures for the MTL 9189 8‑segment redundant fieldbus power supply. It includes safety instructions, system overview, component descriptions, mechanical mounting guidelines, electrical connection details, testing methods, and ATEX compliance information.
The document also lists the available system configurations, part numbers, and technical specifications such as voltage ranges, current capacities, temperature limits, and enclosure requirements, helping installers and service personnel configure the power supply for both general‑purpose and hazardous‑area applications.
| Power module voltage range (28‑32 V version) | 28.0‑32.0 V, 250 mA |
|---|---|
| Power module voltage range (19‑22 V version) | 19.0‑22.0 V, 250 mA |
| Operating temperature range | -20 °C to +60 °C (vertical DIN‑rail) / -20 °C to +50 °C (vertical mounting) |
| Ingress protection rating | IP54 minimum |
| Maximum working voltage | 30 V DC |
The 9189 system is designed to provide power for eight Foundation™ fieldbus H1 segments.
Yes, it is designed for installation in Zone 2 hazardous areas and complies with EN 60079‑0, EN 60079‑15, and ATEX directives.