MTL functional safety management system and SIL 2, SIL 1, SIL 3 products are introduced to protect instrument loops to achieve highest SIL3 safety integrity level.
This manual provides guidance on the application of MTL surge protection devices within functional safety-related loops conforming to IEC 61508:2010 and IEC 61511. It covers system configuration, product selection, and assessment for use in safety applications for the SD, SLP, IOP, and TP series.
No, the devices are regarded as wiring components and do not perform a defined safety function.
The surge protection devices have a hardware fault tolerance of 0.
For an average ambient temperature of 60°C, failure rates should be multiplied by a factor of 2.5.