MTL7700 series shunt diode safety barriers are suitable for applications requiring compliance with US Mine Safety and Health Administration (MSHA) requirements. These products have been certified by MSHA.
The MTL7700 range consists of fourth-generation intrinsically safe shunt-diode safety barriers. The 1-, 2- or 3-channel devices pass electrical signals between safe and hazardous areas while limiting transferred energy to a level that cannot ignite flammable atmospheres.
The instruction manual covers safety considerations, installation, wiring connections, maintenance, fault-finding and equipment and barrier tests. It also includes MSHA information and ATEX safety instructions, plus an appendix of typical wiring connections for specific applications.
| Channels | 1, 2 or 3 |
|---|---|
| Mounting | DIN-rail |
| Power link supply | 24 V dc |
| Maximum barriers per power link | 40 barriers in a single column |
| Maximum input voltage at barrier input terminals | 120 Vrms |
| Zone 2 relay contact rating (MTL7741 to MTL7745) | 60 Vac / 75 Vdc maximum |
| Zone 2 minimum enclosure protection | IP 54 |
They pass electrical signals between safe and hazardous areas while limiting transferred energy to a level that cannot ignite flammable atmospheres.
Yes. Being intrinsically safe, shunt-diode barriers enable maintenance work or calibration to be carried out live without additional precautions.
Section 3 contains a checklist of essential safety factors that must be considered when using MTL7700 barriers as intrinsically safe interfaces.
They must be securely mounted within a suitable dust-tight enclosure in a fresh air area of the mine or an explosion-proof enclosure.