About this manual

This document serves as an application note detailing the principles of earthing for surge protection. It explains how lightning interacts with electronic systems through direct attachment, capacitive/inductive coupling, and resistive coupling (ground potential surges). The text emphasizes that proper installation is critical for the effectiveness of any surge protection device.

The guide covers practical aspects of implementing an earthing system, including structural protection requirements, cable routing strategies to minimize inductance, and bonding techniques. It discusses specific configurations like star-point earthing and provides advice on handling diverse cables and hazardous areas.

What's inside

  • EARTHING FOR SURGE PROTECTION
  • LIGHTNING AND THE NEED FOR SURGE PROTECTION
  • SURGES AND SURGE PROTECTION
  • EARTHING for SURGE PROTECTION in the REAL WORLD
  • SURGE EARTH IMPEDANCE
  • SURGE EARTH POSITION
  • EARTHING SYSTEM CONFIGURATIONS and INSTALLATION

Frequently asked questions

What is the minimum cross section for bonding SPDs to an earth terminal?

The bond cable should have a minimum cross section of 2.5mm².

What is the median current for direct cloud-to-ground lightning strokes in the UK?

In the UK, the median current for these strokes is around 30kA.