MTL MTL700 and 700P Series Shunt-Diode Safety Barriers Instruction Manual

This is an instruction manual, which introduces the characteristics and specifications of the MTL700 and 700P series shunt-diode safety barriers.


MTL MTL700 and 700P Series Shunt-Diode Safety Barriers Instruction Manual - cover page
Brand
MTL
Category
Other
Document type
User Manual
Language
English
Pages
32
File format
PDF
File size
657 KB
Published
31 October, 2023
Updated
31 October, 2023
MD5 checksum
40EDB95D4D604B0A962A3A291BC1FDF6

About this manual

This INM700-10 instruction manual, dated June 2005, covers the MTL700 and 700P Series shunt-diode safety barriers from MTL Instruments Group plc. It describes 1-channel or 2-channel barriers that pass signals between non-hazardous (safe) and hazardous areas by limiting energy transfer.

The manual covers barrier specifications, safety conditions and checks, mounting in enclosed and unenclosed systems, wiring installation, maintenance, fault-finding, and thermocouple, RTD and barrier tests. It also notes a range of five polycarbonate enclosures and a Type N approved steel enclosure.

What's inside

  • Introduction
  • Description
  • Barrier specifications
  • Safety conditions
  • Mounting the barriers (enclosed systems)
  • Mounting the barriers (unenclosed systems)
  • Wiring installation
  • Maintenance
  • Fault-finding
  • Barrier tests

Specifications

Channels1-channel or 2-channel devices
Maximum voltage (UM)250V rms or dc with respect to earth
MTL702 supply voltage20 to 35V dc, positive w.r.t. earth
MTL702 load resistance850Ω maximum
MTL706 output current4 to 20mA
MTL705 output current0 to 20mA

Frequently asked questions

What are MTL700 and 700P Series barriers used for?

They use intrinsically safe techniques to pass electrical signals between non-hazardous (safe) and hazardous areas by limiting energy transfer.

What is UM for MTL700/700P barriers?

For all MTL700/700P barriers, UM is 250V rms or dc with respect to earth.

What supply voltage does the MTL702 require?

The MTL702 requires a supply voltage of 20 to 35V dc, positive with respect to earth.

What should users read before commencing work on a barrier installation?

Users should read Section 4, and particularly the checklist, before commencing work on the barrier installation.

Download PDF (657 KB)

More MTL Manuals


View all MTL manuals →