This is an instruction manual, which introduces the characteristics and specifications of the MTL700 and 700P series shunt-diode safety barriers.
This INM700-10 instruction manual, dated June 2005, covers the MTL700 and 700P Series shunt-diode safety barriers from MTL Instruments Group plc. It describes 1-channel or 2-channel barriers that pass signals between non-hazardous (safe) and hazardous areas by limiting energy transfer.
The manual covers barrier specifications, safety conditions and checks, mounting in enclosed and unenclosed systems, wiring installation, maintenance, fault-finding, and thermocouple, RTD and barrier tests. It also notes a range of five polycarbonate enclosures and a Type N approved steel enclosure.
| Channels | 1-channel or 2-channel devices |
|---|---|
| Maximum voltage (UM) | 250V rms or dc with respect to earth |
| MTL702 supply voltage | 20 to 35V dc, positive w.r.t. earth |
| MTL702 load resistance | 850Ω maximum |
| MTL706 output current | 4 to 20mA |
| MTL705 output current | 0 to 20mA |
They use intrinsically safe techniques to pass electrical signals between non-hazardous (safe) and hazardous areas by limiting energy transfer.
For all MTL700/700P barriers, UM is 250V rms or dc with respect to earth.
The MTL702 requires a supply voltage of 20 to 35V dc, positive with respect to earth.
Users should read Section 4, and particularly the checklist, before commencing work on the barrier installation.