Installation instructions for Lutron wallstations used with GRAFIK Eye 3000 Series and 4000 Series systems, covering wiring, addressing, mounting, and setup.
These instructions cover Lutron wallstations, including NTGRX, EGRX, and GRX models, for use with GRAFIK Eye 3000 Series and 4000 Series systems. They describe Class 2/PELV circuit classification, wiring notes, system maximums, wallbox mounting, addressing, function selection, daisy-chain wiring, and setup-mode communication.
The document also includes model-specific DIP-switch function charts, 3000 Series and 4000 Series wiring diagrams, mounting diagrams, and instructions for putting a wallstation into setup mode.
| Circuit voltage | Does not exceed 24 VAC or 15 VDC |
|---|---|
| Operating temperature | 0 °C to 40 °C |
| Maximum wiring length | 2000 ft. (600 m) |
| Unique GRAFIK Eye addresses per system | 8 |
| Wallstations per system | 16 |
| Wallstations powered by 3000 Series control unit | Maximum of 3 |
| 3000 Series wallstation wiring | Four #18 AWG (1.0 mm2) Class 2/PELV wires |
| 4000 Series wallstation wiring | Two #12 AWG (2.5 mm2) and two shielded #18 AWG (1.0 mm2) Class 2/PELV wires |
| Standard wallbox depth | 2.75 in. (70 mm) |
| EGRX backbox mounting hole spacing | 60.30 mm center to center |
A system can have 16 Wallstations.
The maximum wiring length is 2000 ft. (600 m).
The specified operating temperature range is 0 °C to 40 °C.
A system can have 8 unique GRAFIK Eye addresses.