Manual for the EPCOS BR 7000 power factor controller: installation, connection alternatives, programming, expert modes, interfaces and technical data.
This is the Version 4.0 manual for the EPCOS BR 7000 power factor controller, a panel-mounted instrument for power factor correction systems. According to the general section, the BR 7000 follows the BR6000 series and its main new feature is a 3-phase measuring system, which lets the device be used both as a grid measuring device and as a power factor controller. The manual describes installation, connection alternatives for measuring voltage and current, display functions, manual programming, help and alarm functions, expert and oscilloscope modes, interfaces and test modes, and ends with annexes for troubleshooting, technical data, factory settings and an operation diagram.
| Operating (supply) voltage | 110...440 V AC (+/-10%), 50/60 Hz |
|---|---|
| Measuring voltage | 30...440 V AC (L-N) / 50...760 V AC (L-L), 50/60 Hz |
| Measuring current | 5 A or 1 A (programmable) |
| Switching outputs | 3 x 5 free programmable switching outputs |
| Relays | 1 alarm relay, 1 programmable message relay, 1 relay for the cabinet fan |
| Display | Illuminated graphic display 128 x 64 dot |
| Harmonic display | Up to the 31st harmonic of voltage and current |
| Panel cut-out | 138 x 138 mm according to DIN 43700 / IEC 61554 |
| Dimensions | 144 x 144 x 50 mm |
| Interfaces | 2 integrated separate interfaces |
It is a power factor controller with 3-phase voltage and current measurement, so it can be used as a grid measuring device as well as a power factor controller.
A Windows PC software called BR7000-Soft is enclosed with delivery; it is used for programming the PF controller and for visualization, storage and analysis of grid parameters.
The device is a panel mounting instrument and requires a cut-out of 138 x 138 mm according to DIN 43700 / IEC 61554, fixed with the clamps included in delivery.
Control is possible as 3-phase, 1-phase (balancing) or in mixed mode, and the manual also notes that it can be operated manually or automatically.