EPCOS B44066D1450L400 Harmonic Filter Reactor Datasheet

Technical datasheet for the EPCOS B44066D1450L400 harmonic filter reactor, detailing specifications, characteristics, and installation cautions.


EPCOS B44066D1450L400 Harmonic Filter Reactor Datasheet - cover page
Brand
Epcos
Category
Other Electronics
Document type
Datasheet
Language
English
Pages
5
File format
PDF
File size
111 KB
Published
22 November, 2026
Updated
22 November, 2026
MD5 checksum
0C71A270720C3F9CE2D0A2BE9BD477D0

About this manual

This document is a preliminary datasheet for the EPCOS B44066D1450L400 harmonic filter reactor, designed as an accessory for power factor correction systems. Key characteristics include high linearity, low losses due to aluminum windings, and a standard temperature switch for safety. The device is rated for a voltage of 400V and a frequency of 50Hz.

What's inside

  • Characteristics
  • Technical Data
  • Dimensional drawing
  • Cautions
  • Installation instructions
  • Temperature protection
  • Important notes
  • Trademarks

Specifications

De-tuning factor p14 %
Effective filter output QC50 kvar
Rated voltage VR400 V
Rated frequency50 Hz
Ambient temperature / Insulation class40 °C/H
Capacitance C delta (tot.)855 µF
Inductivity L1.66 mH
Effective current Irms76.9 A
Rated harmonic voltages (3rd/5th/7th/11th/13th)0.5 / 6 / 5 / 3.5 / 3 %
Total losses PD267 W
Total weight38 kg

Frequently asked questions

Does the reactor include a temperature switch?

Yes, it includes a temperature micro switch (NC) as a safety device.

What is the maximum permissible surface temperature?

Surfaces may attain values of up to 260 °C under rated operating conditions or overload.

Is the temperature switch a disconnect device?

No, the integrated temperature switch is a warning device only and will not disconnect the reactor.