Installation instructions for the Enphase CT-100-SPLIT-ROW 100A split-core current transformers used for production and consumption monitoring.
The Enphase CT-100-SPLIT-ROW installation instruction describes how to install a set of three 100A split-core current transformers for production and consumption monitoring with the Enphase IQ Gateway. It explains preparation, wiring and clamping for production CTs on Lines 1, 2 and 3, and installation of consumption CTs on the main supply lines.
The document also gives safety warnings and notes, product specifications, and installation tips for running multiple conductors through one CT and for parallel-connected CTs in 200A services or crowded service panels.
| CT type | Split core |
|---|---|
| CT accuracy (error rate) | <1% |
| Maximum primary current | 100A |
| Turns ratio | 2500 |
| Dimensions | 40.1 x 26.4 x 26.7 mm |
| Aperture | 9.8 mm diameter |
| Maximum conductor size support | 16mm2 |
| CT lead wire length | 4m |
| Primary voltage | 250VAC |
| Frequency | 50-60Hz |
| Operating temperature | -40 to 85 degree C |
| Compliance | CE, RoHS compliant |
| Connection tightening torque | 0.56 Nm |
The document states a CT accuracy (error rate) of less than 1%.
The maximum primary current is 100A.
For production monitoring, the arrow must point toward the load, away from the solar array.
Tighten all connections to 0.56 Nm.