About this manual

Delta Electronics Inc. publishes this instruction sheet for the DOP-107WV, part of the DOP-100 series of high-color, widescreen HMI products. The sheet also includes DOP-103WQ and DOP-110WS in its model tables, and covers safety precautions, communication port pin assignments, part names, installation dimensions, mounting and wiring instructions, and specifications.

Specifications listed for the DOP-107WV include a 7-inch TFT LCD with 800 x 480 pixels, an ARM Cortex-A8 800 MHz CPU, 256 MB flash ROM, 512 MB RAM, a 4-wire resistive touch screen, LAN, USB host and slave ports, and a 3 V CR2032 backup battery. The document also gives panel cutout dimensions, mounting torque, wiring gauge, power supply requirements, and environmental limits.

What's inside

  • Preface
  • Communication Port Pin Assignment
  • Part names
  • Dimensions for Installation
  • Installation and Wiring
  • Specifications

Specifications

Display type7" TFT LCD (65535 colors)
Resolution800 x 480 pixels
Display size154.08 x 85.92 mm
Brightness450 cd/m² (Typ.)
CPUARM Cortex-A8 (800 MHz)
Flash ROM256 Mbytes
RAM512 Mbytes
Touch screen4-wire resistive touch screen, > 10,000,000 operated
Ethernet10/100 Mbps Auto sensing
USB1 USB Slave Ver 2.0, 1 USB Host Ver 2.0
Operating voltage+24 V DC (-15% ~ +15%)
Power consumption8.4 W (Max)
Backup battery3 V lithium battery CR2032 x 1
Operating temperature0°C ~ 50°C
Dimensions (W x H x D)196 x 136 x 39 mm
WeightApprox. 560 g

Frequently asked questions

What should I do when the HMI displays a low battery notification?

Contact local distributors or the Delta customer service center for the replacement; do not change the batteries yourself.

What is the allowable panel thickness for mounting?

The panel thickness should be less than 5 mm.

What torque should be used for DOP-107/DOP-110 mounting screws?

Use 6.17 lb-inch (0.7 N-M) torque for DOP-107/DOP-110 mounting screws.

How should I clean the product?

Use a dry cloth to clean the product.