Delta DVP04PT-H2 Installation Manual

DVP04PT-H2 is able to receive 4 points of resistance temperature detectors (PT100, PT1000, NI100, and NI1000) and convert them into 16-bit digital signals. Besides, through the user of FROM/TO instructions in DVP-EH2 MPU program, the data in DVP04PT-H2 can be read or written. There are 49 16-bit control registers (CR) in it. DVP04PT-H2 displays temperatures in Celsius (resolution: 0.1°C) and Fahrenheit (resolution: 0.1°F).


Brand
Delta
Category
Industrial Supply
Document type
Installation Guide
Language
English
Pages
21
File format
PDF
File size
812 KB
Updated
01 October, 2023
MD5 checksum
AD37902B14C9FC9E3699BC44E2072219

About this manual

The DVP04PT-H2 module receives up to four resistance temperature detector (RTD) inputs (PT100, PT1000, NI100, NI1000) and converts them to 16‑bit digital signals. It can be read or written via FROM/TO instructions in a DVP‑EH2 PLC program and supports RS‑485 communication in ASCII or RTU mode.

The manual provides electrical specifications, installation and wiring instructions, control register descriptions, and PID control settings. It also outlines environmental limits, isolation requirements, and error status codes for safe and reliable operation.

What's inside

  • Electrical Specifications
  • Installation and Wiring
  • Control Register Overview
  • PID Control Registers
  • Temperature / Digital Value Curve
  • Error Status Codes
  • Product Profile & Dimensions
  • Other Specifications

Specifications

Power supply voltage24 VDC (20.4 – 28.8 VDC) (-15 % to +20 %)
Resolution16‑bit (0.1 °C / 0.1 °F)
Output impedance≤ 0.5 Ω
Overall accuracy± 0.6 % full‑scale (0 – 55 °C)
Response time400 ms × number of channels
Isolation voltage500 VDC between digital, analog and ground circuits
Supported communication speeds4,800 – 115,200 bps
Number of sensor channels4 analog input channels

Frequently asked questions

What power supply voltage does the DVP04PT-H2 require?

It requires a 24 VDC supply, acceptable between 20.4 V and 28.8 V with a tolerance of –15 % to +20 %.

How many temperature sensor inputs can the module handle?

The module can receive four RTD inputs (PT100, PT1000, NI100, NI1000).

What communication modes are supported over RS‑485?

Both ASCII and RTU modes are supported, with selectable baud rates from 4,800 bps up to 115,200 bps.