Schneider Electric ATV61 Synchronous and Asynchronous Motor Variable Speed Drive Installation Manual

This document is an installation manual for the ATV 61 synchronous and asynchronous motor inverter with a power range of 55kW (75HP) - 800kW (800HP). It covers the installation steps, rated values, dimensions, and weight of the inverter.


Schneider Electric ATV61 Synchronous and Asynchronous Motor Variable Speed Drive Installation Manual - cover page
Brand
Schneider
Category
Industrial Supply
Document type
Installation Guide
Language
Chinese
Pages
78
File format
PDF
File size
9.4 MB
Updated
29 September, 2023
Model
ATV61
MD5 checksum
807CA60EDDDD0C74395FE18806CF2600

About this manual

Schneider Electric ATV61 is a variable speed drive for synchronous and asynchronous motors. This installation manual covers unpacking, handling, mounting, DC reactor or transformer installation, ratings, dimensions, wiring, optional cards, and electromagnetic compatibility.

It includes safety warnings for qualified personnel, power and control terminal guidance, connection diagrams, and derating information. Programming is covered in a separate programming manual. This manual is written in Chinese.

What's inside

  • Important information
  • Before you begin
  • Drive installation steps
  • Preliminary recommendations
  • Drive ratings
  • Dimensions and weight
  • Installing the DC reactor or transformer
  • Derating by temperature and switching frequency
  • Wiring recommendations
  • Electromagnetic compatibility (EMC) wiring

Specifications

Rated power range55-90 kW (75-125 HP) at 200-240 V; 90-630 kW (125-900 HP) at 380-480 V; 90-800 kW (125-800 HP) at 500-690 V
Line voltage range200-240 V, 380-480 V, 500-690 V

Frequently asked questions

Who is allowed to install or maintain the ATV61 drive?

Only qualified personnel may install, adjust, repair, and maintain the drive.

What must be done before maintaining the drive?

Disconnect all power, lock the breaker open, wait for the charging LED to turn off, then verify DC voltage is below 45 V.

How should an unused drive be powered to preserve capacitors?

If unused for a long time, power it for at least 5 hours every two years.

Is a DC reactor required with three-phase power?

Yes, the DC reactor must be used when the drive is connected to a three-phase power circuit.