Profibus (CME-PD01) User's Manual introduces the overview, installation, communication function, GSD file introduction, error message indication and troubleshooting of CME-PD01.
This is the Traditional Chinese user manual for the Delta CME-PD01, a PROFIBUS-DP communication module used to connect a PROFIBUS-DP system to Delta VFD-E series inverters. The manual introduces the module's LEDs, address setting switches, RS-485 (RJ-45) port and DB9 PROFIBUS-DP interface, and lists the package contents and supported transmission rates from 9.6 kbaud to 12 Mbaud.
The document then describes PROFIBUS and PROFIBUS-DP in general, installation of the CME-PD01, address and inverter communication parameter settings, cyclic PZD data and parameter access via the PKW area, the GSD file and user parameter settings, and troubleshooting through the LED indications, 16-byte diagnostic data and error codes. It closes with the module's dimensions. This manual is written in Chinese.
| Communication transfer rate | 9.6 kbaud to 12 Mbaud |
|---|---|
| PROFIBUS-DP interface | DB9 (9-pin connector) |
| Inverter connection port | RS-485 communication port, RJ45, 8-pin |
| Transmission distance range | 100 m to 1,200 m |
| Address setting | Two rotary switches, ADDH (high 4 bits) and ADDL (low 4 bits) |
| Required inverter firmware | VFD-E version 2.02 or later |
| Package contents | One CME-PD01, one RJ-45 8-pin communication cable, one quick installation guide |
One CME-PD01 unit, one RJ-45 8-pin communication cable and one quick installation guide. If the contents differ, contact your agent or distributor.
The inverter communication format must be (9600, <8,N,2>, RTU).
With two rotary address switches: ADDH sets the upper 4 bits of the address and ADDL the lower 4 bits.
The CME-PD01 has entered test mode; do not set the communication address to 0xFF, set another value and restart the module.