The SOYAL AR-727-CM HTTP Server is a multifunctional device that provides a WEB service interface, cross-platform service, parameter settings, fire alarm unlocking settings, and DI/DO direct query control functions.
This manual describes the SOYAL AR-727-CM HTTP server used with AR-727-CM, AR-727-CM-IO-0804M, and enterprise-series controllers. It explains web-based setup, network settings, RS485 port settings, IO direct control, TCP/IP converter functions, fire alarm linkage, Server/Client mode, Modbus TCP to RTU, and password changes.
It also provides interface screenshots, parameter ranges, default login information, and a short FAQ with RS485 cable and connection recommendations. This manual is written in Chinese.
| Supported controllers | AR-727-CM, AR-727-CM-IO-0804M, and enterprise-series controllers |
|---|---|
| Default IP address | 192.168.1.127 |
| Default HTTP port | 80 |
| TCP/IO control port | 1601 (default) |
| Modbus port | 502 |
| RS485 local port | 1621 (range 1024-65535) |
| Baud rate | 9600 |
| Parity | None (default) |
| Stop bits | 1 (default) |
| UART to network delay time | 10 ms |
| Minimum transfer bytes | 1024 (range 16-1024) |
| Socket timeout | 120 s (range 0-600) |
| Selected node ID | 0 (disabled by default; range 1-254) |
| Maximum controllers per RS485 channel | 8 |
| Total controllers with two channels | 16 |
| RS485 cable distance | 1200 m theoretical; 300 m recommended for parallel wiring |
| Recommended RS485 cable | AWG22 twisted-pair shielded cable |
| Default login | SuperAdm / 721568 (firmware 2020/01/21 and later); admin / admim (earlier firmware) |
The manual recommends connecting up to 8 card readers or controllers per RS485 channel.
RS485 can theoretically reach 1200 m; for parallel wiring over 300 m, the manual recommends an AR-485REP-V3 signal repeater.
The recommended cable is AWG22 twisted-pair shielded cable.
For firmware dated 2020/01/21 or later, the default account is SuperAdm and the default password is 721568.