Toshiba RBC-AMSU51-ES/EN Wired Remote Controller Installation Manual

This document is an installation manual for Mitsubishi Electric wired remote controller. The model of the remote controller is RBC-AMSU51-ES and RBC-AMSU51-EN.


Toshiba RBC-AMSU51-ES/EN Wired Remote Controller Installation Manual - cover page
Brand
Toshiba
Category
Air conditioner
Document type
Installation Guide
Language
Chinese
Pages
34
File format
PDF
File size
4 MB
Published
19 November, 2023
Updated
19 November, 2023
MD5 checksum
C30F5D966A43EE9DD3516A6A27952806

About this manual

This installation manual covers the Toshiba RBC-AMSU51-ES and RBC-AMSU51-EN wired remote controller. It explains installation position and dimensions, remote controller wiring and group control wiring requirements, and installation of a dual remote controller system.

The document also covers initial setup, remote controller screen and part names, initial settings such as room name, clock, contrast, and main/sub unit selection, and the field setting menu for operation modes, filter settings, timer operation mode, DN setting, power consumption data reset, and notice history. This manual is written in Chinese.

What's inside

  • Safety Precautions
  • Accessories
  • Remote Controller Installation Requirements
  • Installation Position and Dimensions
  • Remote Controller Wiring
  • Group Control Wiring Requirements
  • Dual Remote Controller Installation
  • Initial Setup
  • Remote Controller Screen
  • Field Setting Menu

Specifications

Installation height1 to 1.5 m
Mounting hole size4-Ø4.2 x 8
Controller dimensions42 mm x 42 mm x 22 mm
Communication cable typeVCTF: 0.5 mm² to 2.0 mm² x 2
Maximum remote controller cable length500 m
Maximum indoor unit cable length300 m
Maximum total indoor unit cable length400 m
Maximum indoor unit connection length200 m
Group control remote controllersUp to 8 units
Dual remote controller systemUp to 2 remote controllers

Frequently asked questions

Where should the wired remote controller be installed?

Install it vertically on a wall at a height of 1 to 1.5 m so that it can detect the average room temperature. Do not install it in direct sunlight, in contact with outdoor air, behind objects, or in a cold or humid location.

What wiring is required for the remote controller?

Use VCTF cable of 0.5 mm² to 2.0 mm² x 2 and connect the remote controller to the indoor unit. Do not use a direct-connect terminal, and keep the communication wiring away from AC 220-240 V wiring.

How many remote controllers can be used in a group control system?

A group control system can use up to 8 remote controllers connected to the indoor units.

How is a dual remote controller system installed?

Install the main remote controller first, then install the second remote controller of the dual remote controller system. When using the RBC-AMSU51-ES or RBC-AMSU51-EN with another remote controller, set this remote controller as the main remote controller.