Yaskawa PG-X2 Encoder Feedback Option Card Installation Guide

The Yaskawa Electric America, Inc. PG-X2 Encoder Feedback Option Card is a card that mounts on the drive's Control Board and uses the pulse generator (PG) on the motor to correct speed fluctuation caused by motor slip.


Yaskawa PG-X2 Encoder Feedback Option Card Installation Guide - cover page
Brand
YASKAWA
Category
Expansion card
Document type
Installation Guide
Language
English
Pages
8
File format
PDF
File size
114 KB
Published
11 November, 2023
Updated
11 November, 2023
MD5 checksum
3AFA270A482FADAA84C98FE906127912

About this manual

The PG-X2 is an encoder feedback option card from Yaskawa Electric America. It mounts on the drive’s control board and uses the motor’s pulse generator (PG) for speed feedback to correct speed fluctuation caused by motor slip. Phase A and phase B pulse inputs detect motor rotation direction, and the card can be used for flux vector control or V/Hz with PG feedback control.

The installation guide covers receiving, cautions, preliminary installation, mounting, wiring, adjustment, cover reinstallation, programming, and start-up. It also lists encoder feedback parameters and gives requirements for maximum input frequency, signal type and level, oscilloscope test points, and separate PG power supply use.

What's inside

  • Introduction
  • Cautions
  • Precautions and Preliminary Installation
  • PG-X2 Installation
  • Wiring
  • Adjustment
  • Programming
  • Start-up
  • Application
  • Signal type / level requirements

Specifications

Applicable drivesF7, G7, GPD515/G5, G5HHP
Maximum input frequency300 kHz
Encoder output signal voltage+5 VDC to +12 VDC
+12 VDC PG power output200 mA max
+5 VDC PG power output200 mA max
Control signal wiring distance50 m (165 feet) or less
Recommended cableTwisted pair, 22 AWG, with overall shield, such as Belden 9504
TA1/TA2 terminal screw torque1.8 to 2.2 lb-in (0.22 to 0.25 N-m)
TA1/TA2 wire range26 to 16 AWG

Frequently asked questions

Which drives is the PG-X2 applicable to?

The guide lists applicability for F7, G7, GPD515/G5, and G5HHP drives.

What is the maximum input frequency of the card?

The guide states a maximum input frequency of 300 kHz and advises a 20% safety margin.

What encoder signal type does the PG-X2 require?

It requires a quadrature line driver with compliments signal type, and an open collector signal will not work.

How far can control signal wiring run?

Control signal wiring should be limited to 50 m (165 feet) or less.

Download PDF (114 KB)

More YASKAWA Manuals


View all YASKAWA manuals →