WEG AVR-A-OPT-06 400Hz Automatic Voltage Regulator Installation, Operation and Maintenance Manual

This document is the installation, operation and maintenance manual for WEG AVR-A-OPT-06 400Hz.


WEG AVR-A-OPT-06 400Hz Automatic Voltage Regulator Installation, Operation and Maintenance Manual - cover page
Brand
WEG
Category
Other Electronics
Document type
User Manual
Language
English
Pages
57
File format
PDF
File size
3.2 MB
Published
10 November, 2023
Updated
10 November, 2023
MD5 checksum
C8441B5770D9AE812EA937F29A6CE831

About this manual

The WEG AVR-A-OPT-06 400Hz is an automatic analog voltage regulator for brushless synchronous alternators. It uses semiconductor and integrated-circuit control circuits, has no mechanical field-flashing components, and is encapsulated in resin.

This manual covers safety, storage and transport, technical characteristics, nomenclature, protection curves, connection diagrams, dimensions, first use, testing without an alternator, troubleshooting, preventive maintenance, and warranty. The manual is provided in English, Spanish, and Portuguese.

What's inside

  • Safety Information
  • Storage and Transport
  • Introduction
  • Technical Characteristics
  • Connection Diagrams
  • Internal Connection Diagram
  • Dimensions
  • First Use
  • Troubles, Causes and Corrective Action
  • Preventive Maintenance

Specifications

Nominal field current7A
Nominal current with forced ventilation9A
Peak current (max. 1 min)9A
Protection fuse for power supply5A
Sensing voltage range (VRal)160-300 or 320-600 Vac
External voltage controlThrough 5KΩ/3W potentiometer
Sensing power supplySingle Phase
Power supply range (Val)170 to 300Vac
Rectifier gain ratio (Kc)0,45
Maximum field voltage (Vf)76,5 Vdc (Val min); 112,5 Vdc (Val max)
Field resistance @ 20°C6 up 50Ω
Static regulation0,5%
Adjustable dynamic response8 to 500ms
Operation frequency400Hz
Under-frequency protection (U/F)Adjustable via trimpot
Internal percent adjustment of voltageAdjustable via trimpot, for the complete range of Voltage VRal
External percent adjustment of voltage±15% de VRal
Temperature range-40° to +60°C
EMI suppressionEMI filter
Approximate weight480g
Torque specifications for fixing1.8 N*m

Frequently asked questions

What is the rated operation frequency of the AVR-A-OPT-06?

The rated operation frequency is 400 Hz.

What power supply fuse is specified?

The specified fuse is 5 A/250 V.

How is the under-frequency protection set at the factory for 400 Hz operation?

It is adjusted to 10% below nominal frequency, or 360 Hz for 400 Hz operation.

How much external voltage adjustment is available?

External voltage adjustment is ±15% of VRal.

Download PDF (3.2 MB)

More WEG Manuals


View all WEG manuals →