This manual describes the features and specifications of the VARISPEED V7 Compact Sensorless Vector Inverter. The inverter is suitable for a wide range of applications, including fans, pumps and conveyors.
This quick manual is for the Yaskawa CIMR-V7AZ VARISPEED V7 compact sensorless vector inverter. It covers safety information, receiving, mounting, wiring, and operation precautions for 200V and 400V class units.
The listed power ranges are 0.1 to 7.5 kW for 200V class 3-phase, 0.1 to 4.0 kW for 200V class single-phase, and 0.2 to 7.5 kW for 400V class 3-phase. The manual also includes mounting, wiring, and operation precautions, including intake air temperature limits.
| 200V class 3-phase power range | 0.1 to 7.5 kW |
|---|---|
| 200V class single-phase power range | 0.1 to 4.0 kW |
| 400V class 3-phase power range | 0.2 to 7.5 kW |
| Software number for units up to 4.0 kW | 5740 |
| Software number for 5.5 kW and 7.5 kW units | 5750 |
| IP20 intake air temperature limit | below 122°F (45°C) |
| NEMA1 intake air temperature limit | below 105°F (40°C) |
The quick manual covers 200V class 3-phase units from 0.1 to 7.5 kW, 200V class single-phase units from 0.1 to 4.0 kW, and 400V class 3-phase units from 0.2 to 7.5 kW.
Disconnect all power before servicing and wait at least one minute after the power supply is disconnected.
No, do not perform a withstand voltage test on any part of the inverter.
Lift the inverter by the heatsink, not by the plastic case or terminal covers.