Carlo Gavazzi DTA04 Motor Thermistor Relay Datasheet

The DTA04 is a motor thermistor monitoring relay. The DTA can detect if one or more of the motor windings exceeds the winding’s maximum operating temperature by means of one or more PTCs installed inside the motor. Advantages are high operational safety, time and cost savings, ensuring your factory production process won’t be interrupted, two outputs, front mounted dual colour LED.


Carlo Gavazzi DTA04 Motor Thermistor Relay Datasheet - cover page
Brand
CARLO GAVAZZI
Category
RELAY
Document type
Datasheet
Language
Chinese
Pages
7
File format
PDF
File size
747 KB
Published
03 November, 2023
Updated
03 November, 2023
MD5 checksum
30616CEE03FA8CDE86ADE0F5EF0EEEE2

About this manual

The DTA04 is a motor thermistor monitoring relay. It detects when one or more motor windings exceed the maximum working temperature using one or more PTCs installed in the motor. The relay has two complementary outputs and can be set for manual or automatic reset. A front dual-color LED indicates alarm and PTC fault states.

It accepts 18 to 265 Vac/Vdc power and is mounted on a DIN rail. The document includes structure, wiring, operating diagrams, input and output specifications, and compatibility information. This manual is written in Chinese.

What's inside

  • Advantages
  • Applications
  • Structure
  • Function
  • Compatibility and conformity
  • Input
  • Output
  • Operation diagram
  • Wiring diagram
  • Reference

Specifications

Housing materialPA66 or modified PPO
MountingDIN rail (EN 50022)
Protection ratingIP20
TerminalsScrew terminals, AWG30 to AWG14 (0.05 to 2.08 mm2)
Power supply18 to 265 Vac/Vdc, 45 to 65 Hz, or dc
Power consumption2.5 VA (AC) / 1.5 W (DC)
Operating temperature-25 to 60 C
Storage temperature-40 to 80 C
Relative humidity5-95% non-condensing
Max operating altitude2000 m amsl
UV resistanceMust not be exposed to UV
StandardsEN60255-6
CertificationsUL 508, CSA 22.2
CE markingL.V. Directive EN60947-5-1, EMC Directive EN 60947-8
PTC inputs1 to 6 PTCs in series
Cable lengthMax 600 m (1.5 mm2) or 200 m (0.5 mm2)
Overtemperature trip> 3600 ohm
Overtemperature reset< 1580 ohm
Short-circuit protection14 ohm (reset 16 ohm)
Open-circuit detection20 kohm (reset < 18 kohm)
Switching frequency< 1 Hz
Refresh time500 ms
Outputs2 x SPDT electromechanical relay
Contact ratingNEMA B 300, 240 Vac; AC1 8 A @ 250 Vac; DC12 5 A @ 24 Vdc; AC15 2.5 A @ 250 Vac; DC13 2.5 A @ 24 Vdc
InsulationBasic insulation, 2.5 kVrms, 4 kV pulse 1.2/50 us

Frequently asked questions

How many PTC sensors can be connected to the DTA04?

Up to six PTCs can be connected in series.

How is automatic reset enabled?

Short terminals r1 and r2.

What is the overtemperature trip threshold?

The relay trips when resistance exceeds 3600 ohm.

How do the two outputs behave during an alarm?

Output 1 opens and output 2 closes during an alarm.

Download PDF (747 KB)