The DTA04 is a motor thermistor monitoring relay. The DTA can detect if one or more of the motor windings exceeds the winding’s maximum operating temperature by means of one or more PTCs installed inside the motor. Advantages are high operational safety, time and cost savings, ensuring your factory production process won’t be interrupted, two outputs, front mounted dual colour LED.
The DTA04 is a motor thermistor monitoring relay. It detects when one or more motor windings exceed the maximum working temperature using one or more PTCs installed in the motor. The relay has two complementary outputs and can be set for manual or automatic reset. A front dual-color LED indicates alarm and PTC fault states.
It accepts 18 to 265 Vac/Vdc power and is mounted on a DIN rail. The document includes structure, wiring, operating diagrams, input and output specifications, and compatibility information. This manual is written in Chinese.
| Housing material | PA66 or modified PPO |
|---|---|
| Mounting | DIN rail (EN 50022) |
| Protection rating | IP20 |
| Terminals | Screw terminals, AWG30 to AWG14 (0.05 to 2.08 mm2) |
| Power supply | 18 to 265 Vac/Vdc, 45 to 65 Hz, or dc |
| Power consumption | 2.5 VA (AC) / 1.5 W (DC) |
| Operating temperature | -25 to 60 C |
| Storage temperature | -40 to 80 C |
| Relative humidity | 5-95% non-condensing |
| Max operating altitude | 2000 m amsl |
| UV resistance | Must not be exposed to UV |
| Standards | EN60255-6 |
| Certifications | UL 508, CSA 22.2 |
| CE marking | L.V. Directive EN60947-5-1, EMC Directive EN 60947-8 |
| PTC inputs | 1 to 6 PTCs in series |
| Cable length | Max 600 m (1.5 mm2) or 200 m (0.5 mm2) |
| Overtemperature trip | > 3600 ohm |
| Overtemperature reset | < 1580 ohm |
| Short-circuit protection | 14 ohm (reset 16 ohm) |
| Open-circuit detection | 20 kohm (reset < 18 kohm) |
| Switching frequency | < 1 Hz |
| Refresh time | 500 ms |
| Outputs | 2 x SPDT electromechanical relay |
| Contact rating | NEMA B 300, 240 Vac; AC1 8 A @ 250 Vac; DC12 5 A @ 24 Vdc; AC15 2.5 A @ 250 Vac; DC13 2.5 A @ 24 Vdc |
| Insulation | Basic insulation, 2.5 kVrms, 4 kV pulse 1.2/50 us |
Up to six PTCs can be connected in series.
Short terminals r1 and r2.
The relay trips when resistance exceeds 3600 ohm.
Output 1 opens and output 2 closes during an alarm.