Carlo Gavazzi RGC1P Series Proportional Switching Controller Datasheet

This datasheet details the Carlo Gavazzi RGC1P series of 1-pole proportional switching controllers with integrated heatsinks, covering specifications…


Carlo Gavazzi RGC1P Series Proportional Switching Controller Datasheet - cover page
Brand
CARLO GAVAZZI
Category
Other Electronics
Document type
Datasheet
Language
English
Pages
25
File format
PDF
File size
5 MB
Published
24 October, 2026
Updated
24 October, 2026
MD5 checksum
E746F97BE0ACB7D884A62E7BED48BAD5

About this manual

The Carlo Gavazzi RGC1P series consists of 1-pole analog switching AC solid state relays designed for proportional control of 1-phase loads. These controllers feature an integrated heatsink, eliminating the need for external thermal calculations, and offer selectable switching modes including phase angle, full cycle, and soft starting. They are equipped with integrated overvoltage protection and wire bonding technology to reduce maintenance costs and increase operational cycles.

What's inside

  • Benefits
  • Applications
  • Main features
  • Order code
  • Selection guide
  • Structure
  • Features
  • Performance
  • Transfer characteristics
  • Output power dissipation

Specifications

Rated voltage (Ue)85 - 265 VAC, 190 - 550 VAC, 410 - 660 VAC
Rated current15 AAC, 30 AAC, 43 AAC, 50 AAC, 63 AAC
Control input types4-20 mA, 0-5 V, 1-5 V, 0-10 V, external potentiometer
Switching modesPhase angle, distributed full cycle(s), advanced full cycle, soft starting
Isolation voltage4000 Vrms (L1, T1, A1, A2, A3, POT, GND, Us to case)
MountingDIN rail (panel mount also possible)
Overvoltage categoryCategory III, 6 kV
Touch protectionIP20

Frequently asked questions

What are the applications for the RGC1P?

The RGC1P is suitable for injection moulding, PET stretch blow moulding, thermoforming, electrical ovens, furnaces, climatic chambers, duct heating, and air handling units.

Does the RGC1P require an external heatsink?

No, the RGC1P is provided with an integrated heatsink, eliminating the need for the user to calculate the size of heatsink needed.

What is the minimum operational current for the RGC1P?

The minimum operational current is 250 mAAC for the 12 AAC and 30 AAC models, and 500 mAAC for the 42, 50, and 62 AAC models.