ABB Safe-12 12 kV SF6 Insulated Ring Network Cabinet and Compact Switchgear Product Manual

Safe-12 is a 12kV SF6 insulated ring network cabinet and compact switchgear introduced by ABB. The product features are high safety and reliability, compact product structure and maintenance-free design, modular design and flexible function selection.


ABB Safe-12 12 kV SF6 Insulated Ring Network Cabinet and Compact Switchgear Product Manual - cover page
Brand
ABB
Category
switch
Document type
Product Leaflet
Language
Chinese
Pages
22
File format
PDF
File size
3.6 MB
Published
03 November, 2023
Updated
03 November, 2023
MD5 checksum
F9F64C7A08378E3E94D8C51474AC3109

About this manual

ABB introduced its SafeRing/SafePlus SF6-insulated ring network cabinets and compact switchgear to the Chinese market in 2001. In 2018 it launched Safe-12, designed for 12 kV systems and based on experience from those products. The manual describes a fully insulated and sealed design with an IP67 gas tank, mechanical and electrical interlocks, low SF6 leakage, arc protection, a 325 mm unit width, maintenance-free live parts and modular functional units.

The document covers the overview, technical parameters, functions and configuration, outdoor switch stations and equipment installation. It details the C load-break switch unit, the F load-break switch-fuse combination unit and the V vacuum circuit breaker unit, together with their standard and optional configurations and interlock conditions. This manual is written in Chinese.

What's inside

  • Overview
  • Technical Parameters
  • Functions and Configuration
  • C Unit – Load Break Switch Unit
  • F Unit – Load Break Switch-Fuse Combination Unit
  • V Unit – Vacuum Circuit Breaker Unit
  • Unit Interlocks
  • Outdoor Switch Station
  • Equipment Installation

Specifications

Rated voltage12 kV
Internal busbar current630 A
SF6 gas pressure at 20°C1.3 bar (12 kV)
Annual SF6 leakage rate0.01% per year
Arc test20 kA, 1 s
SF6 gas tank protection ratingIP67
Switchgear enclosure protection ratingIP4X
Interval unit width325 mm
Cable bushing standardDIN 47636 T1 and T2 / EDF HN 525-61
Maximum fuse rating for transformer protection12 kV, maximum 100 A fuse

Frequently asked questions

What voltage is the Safe-12 designed for?

The Safe-12 is designed for 12 kV systems.

What is the protection rating of the SF6 gas tank?

The SF6 gas tank has an IP67 protection rating.

How wide is each interval unit?

Each interval unit is 325 mm wide.

What is the SF6 gas pressure at 20°C?

The SF6 gas pressure is 1.3 bar at 20°C for 12 kV.

Download PDF (3.6 MB)

More ABB Manuals


View all ABB manuals →