Instruction manual. Introduces the basic functions, installation, use and maintenance methods of the Ekip protection release.
This ABB instruction sheet covers the Ekip protection release for the SACE Emax 2 circuit breakers in the E1.2, E2.2, E4.2 and E6.2 sizes. It shows how the release is fitted, with numbered drawings and a tightening torque of 0.5 Nm (4.4 lb in) for the fixing screws.
A second part explains switching on and running the test procedure with the Ekip TT unit, which is to be ordered separately. The checks differ for Ekip Touch/LCD, where the main page, date/time and protections are verified on the display, and for Ekip Dip, where the protections are set according to the installation and the L, S, I and G LEDs must be off. Instructions are given in Italian, English, German, French and Spanish, and refer to the installation manual for further information. This manual is written in Italian.
| Fixing screw tightening torque | 0.5 Nm (4.4 lb in) |
|---|---|
| Ekip protection release versions | Ekip Dip, Ekip Touch/LCD, Ekip TT |
Wait 5 seconds after disconnecting Ekip TT, then press the "i TEST" button (4) and check that the power LED (3) is on fixed.
The screws are tightened to 0.5 Nm, equivalent to 4.4 lb in.
They must be off; if they are on, even partially, the manual should be consulted.
No, Ekip TT is to be ordered separately.