Toshiba HWT-601F21SM3W-E / HWT-1101F21SM3W-E Air to Water Heat Pump Hydro Unit Installation Manual

This manual provides detailed installation instructions for Hydro Unit, including equipment installation, group control and start-up configuration


Toshiba HWT-601F21SM3W-E / HWT-1101F21SM3W-E Air to Water Heat Pump Hydro Unit Installation Manual - cover page
Brand
Toshiba
Category
Water heater
Document type
Installation Guide
Language
English
Pages
39
File format
PDF
File size
9.5 MB
Published
03 November, 2023
Updated
03 November, 2023
MD5 checksum
0C47213C477362C2D245835995007370

About this manual

The Toshiba Air to Water Heat Pump Hydro Unit is an all-in-one Hydro Unit used with a separate Outdoor Unit. This Installation Manual covers models HWT-601F21SM3W-E, HWT-601F21ST6W-E, HWT-1101F21SM3W-E, HWT-1101F21MM3W-E, HWT-1101F21ST6W-E, HWT-1101F21MT6W-E, HWT-1101F21ST9W-E and HWT-1101F21MT9W-E. It is intended for residential use and describes installation of the Hydro Unit; installation of the Outdoor Unit follows its own manual.

The manual includes sections on general information, accessory parts, installation preparations, safety precautions, example Hydro Unit installation, Hydro Unit installation, start up and configuration, maintenance, troubleshooting, and technical parameters. It also gives requirements for water piping, electrical work, grounding, refrigerant R32 handling, DHW and space-heating pressures, and minimum circulating water flow.

What's inside

  • General information
  • Accessory parts
  • Preparations for installation
  • Precautions for safety
  • Example of Hydro Unit installation
  • Hydro Unit installation
  • Start up and configuration
  • Maintenance
  • Troubleshooting
  • Technical parameters

Specifications

RefrigerantR32
Maximum inlet water pressure for DHW0.6 MPa
Maximum inlet water pressure for space heating0.25 MPa
Minimum inlet water pressure for space heating0.05 MPa
Minimum circulating water flow rate (11 kW)13 L/minute or more
Hydro Unit dimensions (H x W x D)1,700 x 600 x 670 mm

Frequently asked questions

What refrigerant is used in the Air to Water Heat Pump?

The system uses HFC refrigerant R32.

What is the maximum inlet water pressure for DHW?

The maximum inlet water pressure for DHW is 0.6 MPa.

How long before startup should the main power supply be turned on?

Turn on the main power supply up to 12 hours before the system is started, and keep it on during use.

What type of water circuit is required?

The system is designed around a closed water circuit; an open circuit design should not be used.